Set each relay for 24 or 48vdc operation using the dip switch located in the center of the URC1A. Refer to the following table.
RELAY
NUMBERSWITCH
NUMBEROPERATING
VOLTAGESWITCH
SETTING
1
1
24
ON
48
OFF
2
2
24
ON
48
OFF
3
3
24
ON
48
OFF
4
4
24
ON
48
OFF
All 4 of the relays have 4 sets of form C contacts. Use the following table for wiring.
RELAY
CONTACT
SETCOMMON
NORMALLY
OPENNORMALLY
CLOSEDCOIL
+COIL
-
1
1
45
43
47
56
55
2
46
44
48
3
51
49
53
4
52
50
54
2
1
31
29
33
42
41
2
32
30
34
3
37
35
39
4
38
36
40
3
1
17
15
19
28
27
2
18
16
20
3
23
21
25
4
24
22
26
4
1
3
1
5
14
13
2
4
2
6
3
9
7
11
4
10
8
12
URC1A ![]() |
||
| GENERAL | Size | 6.08"L x 1.4"W x 5.6"H |
| Weight | 5.5oz | |
| Mounting | Any type 10 mounting shelf | |
| Operating voltage | 24 or 48 vdc | |
| Power consumption (max. per card) |
@24vdc: 75mA | |
| @48vdc: 85mA | ||
| RELAY COILS | Coil | 1200 ohms |
| Pick-up voltage | 19.2v | |
| Drop-out voltage | 2.4v | |
| Operate time | 10msec | |
| Release time | 5msec | |
| CONTACT RATING | @30vdc | 1amp |
| @125vac | 0.5amp | |
![]() |
![]() |